1. General
PZ42L-E3 Series power analyzer specializes in measuring the data of all kinds of AC networks, such as the currents, the voltages, the powers, the energies etc... It may be used for local display, or it is connected with the control equipment in measuring and controlling system.
They are a kind of programmable analyzer. With the 4 key on the front, we can set their parameters according to the network which we measure. They have many option functions. They can be equipped RS-485 communication with Modbus-RTU protocol; or they can output analog signal or relay signal.
They are a kind of analyzer with excellent cost performance, since they regroup the functions of traditional electric transmitter and digital meters. Therefore they are widely being used in kinds of control system, SCADA system and power management system.
2. Technical parameters
Technical parameters | Value |
Input | Network | Single-phase network; 3-phase balanced network 3-phase unbalanced, 3 wires; 3-phase unbalanced, 4 wires |
Measurable | 26 parameters (3I, 6U, F, 4P, 4Q, 4cos, 4E) |
Frequency | 45 ~ 65Hz |
Voltage | AC 100V, 400V (programmable) |
Overload: 480V (continuous); 800V during 1s |
Consumption: < 0.2VA |
Current | Rating: AC 1A, 5A (programmable) |
Overload: 6A (continuous); 50A during 1s |
Consumption: < 0.2VA |
Thermal drift | <200ppm |
Transformation ratio | Programmable |
Options | Analog output | 1 or 2 outputs, 0 ~ 20mA, 4 ~ 20mA programmable |
Load capacity: ≤500Ω |
Logic output (DO) | 2 relays NO contact outputs (for remote terminal) |
Contact capacity: AC 250V/3A, DC 30V/3A |
Alarm output | the alarm of over voltage, under voltage and over current |
Communication | RS485 (Modbus-RTU protocol) |
Logic input (DI) | 2 or 4 dry contacts (with 5V power) |
Pulse | 2 pulse outputs (open-collector), |
Pulse constant: 10000, 40000, 160000 imp/kWh |
Display | LED, LCD |
Precision | 0.5 (F: 0.05Hz; kVar: 1) |
Power supply | AC/DC 85 ~ 270V; Consumption ≤ 4VA |
Test voltage | 2kVAC/min (voltage input / power; between current inputs) |
1.5kVAC/min (outputs / power) |
Insulation | input / housing and output / housing >100MΩ |
Environment | Work T: -10°C ~ +45°C |
Storage T: -20°C ~ +70°C |
Relative humidity: 5% ~ 95% (no condensation) |
Altitude: ≤2500m |
3. Options
- Communication (/C) : RS485 (Modbus-RTU);
1 start bit, 8 data bit, 1 stop bit, no parity,
speed (1200/2400/4800/9600/19200)
- Alarm output(/J): 1 passive relay (1A/30VDC, 1A/250VAC):
alarms of over voltage, low voltage and over current;
The hysteresis and the delay can be set
- Analog output(/M): DC4 ~ 20mA, DC0~20mA (load < 600Ω),
DC0 ~ 5V,DC1 ~ 5V (load > 1kΩ)
- Logic options(/K): 2DI/2DO;
DI: dry contact Input, supplied inside, optoisolator;
DO: NO-NC contact; 1A/30VDC,5A/250VAC ( to control other equipments)
4. Order examplee
Before your order, please inform us the range of current inputs and voltage inputs and options you need.
For example:
Need the 3 phase 96 model ammeter with RS485 communication, 2DI/2DO and LCD display, the range of current is 0-5A
The product type is PZ96L-E3/KC
5. Free Software
Use our free software to realize reading or setting our power analyzers on computer. (Please download free software on our website)
6.SIZE
Panel size:120*120mm
Cut size:108*108mm
Depth:85mm
Other size: 72x72mm, 80x80mm,120x120mm, 144*144mm